| CVE |
Vendors |
Products |
Updated |
CVSS v3.1 |
| Multiple buffer overflows in the F1BookView ActiveX control in F1 Bookview in Schneider Electric ProClima before 6.2 allow remote attackers to execute arbitrary code via the (1) Attach, (2) DefinedName, (3) DefinedNameLocal, (4) ODBCPrepareEx, (5) ObjCreatePolygon, (6) SetTabbedTextEx, or (7) SetValidationRule method, a different vulnerability than CVE-2015-8561. |
| Buffer overflow in Schneider Electric IMT25 Magnetic Flow DTM before 1.500.004 for the HART Protocol allows remote authenticated users to execute arbitrary code or cause a denial of service (memory corruption) via a crafted HART reply. |
| Schneider Electric StruxureWare Building Expert MPM before 2.15 does not use encryption for the client-server data stream, which allows remote attackers to discover credentials by sniffing the network. |
| Untrusted search path vulnerability in Schneider Electric Wonderware System Platform before 2014 R2 Patch 01 allows local users to gain privileges via a Trojan horse DLL in an unspecified directory. |
| Schneider Electric InduSoft Web Studio before 7.1.3.4 SP3 Patch 4 and InTouch Machine Edition 2014 before 7.1.3.4 SP3 Patch 4 store cleartext OPC User credentials in a configuration file, which allows local users to obtain sensitive information by reading this file. |
| Stack-based buffer overflow in the GoAhead Web Server on Schneider Electric Modicon M340 PLC BMXNOx and BMXPx devices allows remote attackers to execute arbitrary code via a long password in HTTP Basic Authentication data. |
| Schneider Electric InduSoft Web Studio before 7.1.3.4 SP3 Patch 4 and InTouch Machine Edition 2014 before 7.1.3.4 SP3 Patch 4 transmit cleartext credentials, which allows remote attackers to obtain sensitive information by sniffing the network. |
| Schneider Electric InduSoft Web Studio before 7.1.3.4 SP3 Patch 4 and InTouch Machine Edition 2014 before 7.1.3.4 SP3 Patch 4 provide an HMI user interface that lists all valid usernames, which makes it easier for remote attackers to obtain access via a brute-force password-guessing attack. |
| Multiple buffer overflows in Schneider Electric VAMPSET before 2.2.168 allow local users to gain privileges via malformed disturbance-recording data in a (1) CFG or (2) DAT file. |
| The Schneider Electric Telvent SAGE 3030 RTU with firmware C3413-500-001D3_P4 and C3413-500-001F0_PB allows remote attackers to cause a denial of service (temporary outage and CPU consumption) via malformed DNP3 traffic. |
| Multiple buffer overflows in ActUWzd.dll 1.0.0.1 in Mitsubishi MX Component 3, as distributed in Citect CitectFacilities 7.10 and CitectScada 7.10r1, allow remote attackers to execute arbitrary code via a long string, as demonstrated by a long WzTitle property value to a certain ActiveX control. |
| The installer routine in Schneider Electric MiCOM S1 Studio uses world-writable permissions for executable files, which allows local users to modify the service or the configuration files, and consequently gain privileges or trigger incorrect protective-relay operation, via a Trojan horse executable file. |
| Schneider Electric StruxureWare SCADA Expert Vijeo Citect 7.40, Vijeo Citect 7.20 through 7.30SP1, CitectSCADA 7.20 through 7.30SP1, StruxureWare PowerSCADA Expert 7.30 through 7.30SR1, and PowerLogic SCADA 7.20 through 7.20SR1 do not properly handle exceptions, which allows remote attackers to cause a denial of service via a crafted packet. |
| Schneider Electric Vijeo Citect 7.20 and earlier, CitectSCADA 7.20 and earlier, and PowerLogic SCADA 7.20 and earlier allow remote attackers to read arbitrary files, send HTTP requests to intranet servers, or cause a denial of service (CPU and memory consumption) via an XML document containing an external entity declaration in conjunction with an entity reference, related to an XML External Entity (XXE) issue. |
| Schneider Electric Trio J-Series License Free Ethernet Radio with firmware 3.6.0 through 3.6.3 uses the same AES encryption key across different customers' installations, which makes it easier for remote attackers to defeat cryptographic protection mechanisms by leveraging knowledge of this key from another installation. |
| The Schneider Electric M340 PLC modules allow remote attackers to cause a denial of service (resource consumption) via unspecified vectors. NOTE: the vendor reportedly disputes this issue because it "could not be duplicated" and "an attacker could not remotely exploit this observed behavior to deny PLC control functions. |
| The client in Schneider Electric Software Update (SESU) Utility 1.0.x and 1.1.x does not ensure that updates have a valid origin, which allows man-in-the-middle attackers to spoof updates, and consequently execute arbitrary code, by modifying the data stream on TCP port 80. |
| The Schneider Electric Magelis XBT HMI controller has a default password for authentication of configuration uploads, which makes it easier for remote attackers to bypass intended access restrictions via crafted configuration data. |
| Heap-based buffer overflow in RFManagerService.exe in Schneider Electric Accutech Manager 2.00.1 and earlier allows remote attackers to execute arbitrary code via a crafted HTTP request. |
| Schneider Electric Modicon Quantum PLC does not perform authentication between the Unity software and PLC, which allows remote attackers to cause a denial of service or possibly execute arbitrary code via unspecified vectors. |